Type | Double-Acting(Outputs air to both sides of a piston actuator). |
Input Signal | Standard Analog:4...20 mA DC, 2-wire (HART) or 4-wire. Digital:PROFIBUS PA, FOUNDATION Fieldbus, PROFINET (as separate communication modules). |
Supply Pressure | Operating Range:1.4...7 bar (20...100 psi) Maximum:10 bar (145 psi) |
Air Consumption | At Steady State:Approx. 0.12 Nm³/h (0.07 scfm) During Action:Depends on actuator size and travel speed. |
Output Air Flow | Max. for Double-Acting:Approx. 140 Nl/min (5 scfm) with supply ≥ 4 bar. |
Ambient Temperature Range | Standard:-30 ... +80 °C (-22 ... +176 °F) Extended:-40 ... +80 °C (-40 ... +176 °F) option available. |
Valve Travel Range | Mechanically Adjustable:3...150 mm (0.12...5.91 in). Rotary Actuators:30° to 120° (direct mount). |
Linearity / Hysteresis | Typically ≤ 0.5% of span (with optimized auto-calibration). |
Dead Band | Adjustable, typically ≤ 0.1%. |
Characteristic | Linear, equal percentage (1:25, 1:33, 1:50), quick opening, user-defined (up to 25 breakpoints). |
Communication & Diagnostics | Standard:HART protocol (5...8) via analog line. Optional Plug-in Modules:PROFIBUS PA, FOUNDATION Fieldbus, PROFINET. Integrated Diagnostics:Monitoring of travel, operating time, alarm counts, partial stroke test (PST) capability. |
Enclosure & Protection | Housing:Aluminum, powder-coated. Protection Class:IP66 / NEMA 4X(Type 4X) with sealed cable entries. Optional:Explosion-proof versions (Ex d/Ex i). |
Mounting | Direct mounting on linear (ISO 5211) and part-turn (VDI/VDE 3845) actuators. |
Certifications | Standard:CE, UKCA, RoHS. Common Options:ATEX, IECEx, FM, SIL 2/3 (per IEC 61508/61511). |
Power Requirements | For 4...20 mA HART:Requires external 24 V DC supply in 4-wire mode. In 2-wire mode, powered from the current loop. |