Customization: | Available |
---|---|
After-sales Service: | 1 Year |
Warranty: | 1 Year |
Still deciding? Get samples of $ !
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Step | Procedure | Details |
1 | Verify Compatibility | Confirm KCD2-SCD-EX1 matches hazardous area device specifications and system requirements. |
2 | Mounting | Install on DIN rail (EN 60715) in safe area. Ensure vertical orientation and adequate ventilation. |
3 | Wiring Preparation | Use 0.25-2.5mm² (24-14 AWG) copper conductors. Strip 7mm insulation. |
4 | Power Connection | Connect 20-30V DC power to terminals 9(+) and 10(-). Maintain polarity. |
5 | Input Wiring | Connect field device to terminals 1(+) and 2(-) for Ex i input. |
6 | Output Wiring | Connect control system to terminals 3(+) and 4(-) for 4-20mA output signal. |
7 | Grounding | Establish protective earth connection via DIN rail or terminal 11 (M4 screw). |
8 | Intrinsic Safety Verification | Ensure loop parameters comply with Ex ia IIC T4 Ga certification (FM/CSA/IECEx/ATEX). |
9 | Jumper Configuration | Set current limit via JP1/JP2 jumpers: 250Ω (default) or 500Ω for higher loop resistance. |
10 | Functional Test | Apply power, validate 4-20mA output corresponds to field device signal. Check LED status (green=OK). |