Step | Action | Description |
1 | Mount the gauge | Install vertically on the tank nozzle using appropriate flanges or threaded connections. Ensure alignment with process fluid flow. |
2 | Connect electrical | Wire the 4-20mA output signal to the control system. Supply 12-30V DC power per terminal markings. |
3 | Zero calibration | With the chamber empty, adjust the zero screw or use HART communicator to set 4mA output. |
4 | Span calibration | Fill the chamber to maximum level and adjust the span screw or HART communicator to set 20mA output. |
5 | Set density | Input specific gravity/density of the measured liquid via HART communicator configuration menu. |
6 | Verify operation | Observe level changes while filling/emptying the chamber. Confirm linear 4-20mA response. |
7 | Enable damping | Adjust signal damping (if required) via HART to stabilize fluctuating readings. |
8 | Maintenance | Periodically clean the float chamber, inspect for corrosion, and verify calibration annually. |