Customization: | Available |
---|---|
Brand: | Samson |
Power: | Pneumatic |
Still deciding? Get samples of $ !
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
SPECIFICATIONS | DETAILS |
Input Signal | 4 - 20 mA |
Valve Travel | 3.6 - 300 mm (linear) 24 - 100° (angular) |
Supply Pressure | 1.4 - 7 bar |
Maximum Output Pressure | 0 - 6 bar |
Electrical Load | Small two-wire system, 410 Ω |
Protection Level | IP66 |
Operating Temperature Range | -40°C to 80°C |
Communication Protocol | HART |
Mounting Standards | For linear actuators: according to IEC 60534-6, VDI/VDE 3847, or Samson integral attachment For rotary actuators: according to VDI/VDE 3845 |
Explosion Protection | ATEX EExi/EExA/nl, FM/intrinsic safety/spark-free, ATEX EExd with field barrier (see type 3731-3) |
Position Sensing | Non-contact |
Housing Material | Die-cast aluminum (standard), stainless steel (optional) |
Adjustment Functions | Adjustable output pressure limitation, adjustable tight-closing function, automatic zero monitoring |
Diagnostic Function | Integrated expert plus diagnostics, complies with NAMUR recommendation NE 107 |
Other Features | Integrated temperature sensor and running time counter, two standard programmable position alarms |