Step | Description |
1 | Ensure installation environment meets specifications (temperature: -40°C to +70°C; humidity ≤95% non-condensing) |
2 | Verify flowmeter arrow direction matches fluid flow direction |
3 | Install supporting pipe brackets within 1 meter upstream/downstream to minimize mechanical stress |
4 | Use compatible gaskets matching process media (PTFE/graphite for corrosive fluids) |
5 | Maintain minimum straight pipe runs (10D upstream/5D downstream from electrodes) |
6 | Ground sensor properly using dedicated grounding lug (10 AWG minimum wire) |
7 | Connect transmitter using shielded twisted pair cable (18-12 AWG) with separate conduit for power/signal |
8 | Configure transmitter settings via AMS TREX device: set units, density parameters, output scaling |
9 | Perform zero calibration with filled/no-flow condition (fluid temperature must stabilize ±2°C) |
10 | Conduct flow verification using Hart communicator (check PV, SV, TV values) |
11 | Apply insulation jacket if operating below ambient dew point |
12 | Implement lightning protection for outdoor installations (Class II surge arrestors) |