Product Type | Intelligent valve positioner |
Communication Protocols | HART, Profibus PA, Foundation Fieldbus H1, FoxCom (for certain configurations) |
Input/Communication Examples | E.g., for HART communication (4 - 20 mA), it can be specified as "H" in the part number configuration. Different letters in the part number represent different communication types, such as "D" for no communication, "P" for PROFIBUS - PA, etc. |
Additional Inputs/Outputs | Options include position feedback 4 - 20 mA and one binary output for alarm (represented by "F" in part number), two switch outputs, etc. Different letters in the part number represent different additional I/O configurations |
Built-in Limit Switch | Can be without built-in limit switch ("S" in part number), or inductive compliant with NAMUR standard ("T", "U", etc. for different inductive types) |
Cable Entry | E.g., M20 x 1.5 with one plastic cable gland ("7" in part number), M20 x 1.5 without cable gland ("1" in part number), 1/2’’ - 14NPT adapter ("6" in part number) |
Electrical Classification | E.g., II 2 G Ex ia IIC T4 Gb according to ATEX (represented by "EA4" in part number). Can be no specific classification ("ZZZ") in some cases |
Attachment Kit | Can be ordered as auxiliary ("N" in part number) |
Manifold | Pneumatic connection 1/4 - 18 NPT made of an additional manifold ("Y" in part number), G1/4 (standard pipe thread) can be another option ("R" in part number) |
Stroke Range | 8 to 260 mm (linear), up to 95° (angular, extendable to 300° on request) |
Supply Air Pressure | Up to 6 bar, extendable to 7 bar with a spool valve |
Actuator Compatibility | Linear actuators (NAMUR standard), rotary actuators (VDI/VDE standards) |
User Interface | Multi-lingual graphical LCD with three-key navigation or four-button operation. Display is visible even with cover closed |
Configuration Methods | Local keys, handheld terminal, PC, infrared interface |
Protection Level | IP65 (IP66 optional), NEMA 4X |
Explosion-proof Certification | ATEX, FM/CSA (intrinsic safety), approved for SIL applications up to SIL 3 |
Diagnostics | Comprehensive diagnostics, predictive maintenance via Valcare™ and Valve Monitor DTM |
Nonlinearity | < 0.4% of stroke range (end-based straight line) |
Hysteresis | < 0.3% of stroke range |
Dimensions (D x W x H) | E.g., 17.60 cm x 12 cm x 12.13 cm (for some models) |