Step | Procedure | Details |
1 | Pre-Installation Check | Verify model F300, DN80 flange rating, process fluid compatibility, and ambient conditions. |
2 | Mounting Orientation | Install vertically with upward flow direction or horizontally per arrow marking on flowmeter. |
3 | Piping Alignment | Use support brackets to prevent stress. Maintain 10x pipe diameter straight run upstream and 5x downstream. |
4 | Flange Connection | Use ISO 5211 DN80 flanges with 16mm bolts (8x M16). Tighten diagonally to 70 N·m torque. |
5 | Electrical Wiring | Connect 18-12 AWG shielded cable to terminal box (IP66/67). Follow EN/AS/NZS/IEC 60079 series for hazardous areas. |
6 | Grounding | Install 2.5 mm² copper ground wire between flowmeter housing and facility ground point. |
7 | Power Supply | Connect 18-36 VDC (24V typical) to terminals +V/-V. Current consumption <35mA. |
8 | Configuration | Use ProLink III or AMS Device Manager to set units (kg/h, lb/min, etc.), density range (0-3g/cm³), and output (4-20mA, HART). |
9 | Zero Calibration | Perform static zero adjustment via terminal box pushbuttons or software after 30-minute warmup. |
10 | Operation Test | Gradually increase flow from 0% to 100% while monitoring output via HART (PV 4-20mA = 0-100% flow rate). |
11 | Maintenance | Annual inspection: verify grounding resistance <1Ω, check for coating buildup, recalibrate if deviation >±0.15% of rate. |