Step | Procedure | Details |
1 | Installation | Mount positioner on valve actuator using appropriate hardware. Ensure proper alignment. |
2 | Pneumatic Connections | Connect supply air (1.4-7 bar) to port 1. Link output ports 2/3 to actuator. |
3 | Electrical Connections | Wire 4-20mA control signal to terminals 11(+) and 12(-). Apply 24V DC power. |
4 | Initialization | Press up and down buttons simultaneously for 3s to enter initialization mode. |
5 | Auto Calibration | Select "AutoCal" from menu. Allow positioner to automatically calibrate travel range. |
6 | Manual Calibration (Optional) | Manually set 0% (down button) and 100% (up button) positions if needed. |
7 | Set Characteristic Curve | Choose linear/equal percentage/quick opening via menu configuration. |
8 | Operation | Input 4mA (0%) to 20mA (100%) control signal. Verify smooth valve movement. |
9 | Fault Diagnosis | Check LCD status codes: ERR1 (mech issue), ERR2 (sensor error), ERR3 (pressure fault). |
10 | Maintenance | Clean air filter annually. Verify stem feedback linkage tightness quarterly. |