Step | Procedure | Details |
1 | Mount the transmitter | Install on a stable surface or pipeline using appropriate brackets. Ensure process connection matches the media. |
2 | Electrical connections | Connect power supply (10.5-42 V DC) to terminals +ve (pin 1) and -ve (pin 2). Use shielded cable for signal lines. |
3 | Apply pressure | Slowly introduce process pressure to avoid shock. Verify pressure limits (0-100% of calibrated range). |
4 | Configuration | Use HART communicator (HT3x) to set parameters: range, units, damping, output linear/square root. |
5 | Calibration | Perform zero and span calibration via HART menu: "Sensor Trim" -> "Zero Trim" / "Span Trim". |
6 | Output verification | Check 4-20 mA output corresponds to applied pressure using multimeter or control system. |
7 | Seal adjustment | Apply thread sealant to NPT connections. Torque wrench to 15-20 Nm for ½" NPT threads. |
8 | Loop test | Simulate 0%/50%/100% pressures and validate control system responses. |
9 | Maintenance | Perform annual recalibration. Clean diaphragm with isopropyl alcohol if contaminated. |