Customization: | Available |
---|---|
Customized: | Customized |
Certification: | CE |
Still deciding? Get samples of $ !
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Step | Description |
1 | Mount the TS600 positioner on the actuator using appropriate brackets, ensuring proper alignment and secure fastening. |
2 | Connect pneumatic supply lines to the INPUT (SUP) port and actuator ports (OUT1/OUT2). Verify air pressure (1.4~7 bar). |
3 | Wire electrical connections: attach 4-20mA/HART signal cables to terminals 31(+) and 32(-). Ensure 9-30V DC power supply. |
4 | Power on the device. Use the push-button or HART communicator to enter configuration mode (display shows "CFG"). |
5 | Select actuator type (linear/rotary) and stroke range via menu navigation. Confirm with long button press. |
6 | Perform auto-calibration: initiate "CAL" mode, allow full actuator travel. LED flashes during calibration (3-5 minutes). |
7 | Verify calibration by applying 4mA (0%), 12mA (50%), and 20mA (100%) signals. Check physical valve position alignment. |
8 | Adjust feedback potentiometer if needed using zero/span screws. Ensure mechanical pointer matches valve position. |
9 | Configure additional parameters (split range, response speed, fail-safe action) via HART interface if required. |
10 | Seal housing cover, tighten to IP66 protection rating. Perform final operational test with signal ramp-up/down cycles. |