Attribute | Description |
Model | 7MF4033-1EA00 |
Brand | S-iemens |
Series | SITRANS DS III |
Type | Pressure Transmitter |
Measurement Medium | Gas, Vapor, Liquid |
Operation Steps | Instructions |
Initial Setup | 1. Remove the protective cover by loosening the two screws on top. 2. Ensure the keyboard lock is unlocked for key operation. |
Display Modes | Use the [M] key to select display modes, including current value (mA), percentage of measured range (%), and pressure units. Adjust with [↑] and [↓] keys. |
Zero and Span Adjustment | 1. Zero adjustment: Set the transmitter to mode 02 (zero set), provide a reference pressure, and press [↑] and [↓] simultaneously for 2 seconds to set zero to 4mA. 2. Span adjustment: Set the transmitter to mode 03 (span set), provide a reference pressure corresponding to the full scale, and press [↑] and [↓] simultaneously for 2 seconds to set span to 20mA. Confirm settings with the [M] key. |
Measurement and Display | The transmitter converts the measured pressure into a current signal (4-20 mA) for output. The display shows the measured value, engineering units, sign, operating status, and operating mode. |
Fault Indication | If a hardware or software fault occurs, the display will show "Error" with a scrolling message indicating the error type. Diagnostic information can also be obtained via HART communication. |
Keyboard Lock/Unlock | To lock the keyboard, set the transmitter to mode 10 and press the [M] key for 5 seconds. To unlock, repeat the same procedure. |
HART Communication | The transmitter supports HART communication for parameter setting, monitoring, and diagnostics. Communication can be established using a HART communicator. |
Maintenance and Troubleshooting | Regularly check the zero point of the instrument for fault diagnosis. Perform internal self-tests to detect faults such as sensor damage or HW/FW errors. Refer to the manual for troubleshooting and maintenance procedures. |