Step | Procedure |
1 | Unpacking & Inspection: Check package contents against shipping list. Inspect for physical damage during transit. |
2 | Mounting: Install on vertical process pipe or horizontal manifold. Use appropriate brackets (model AB201/AB202). Ensure process connection matches transmitter thread (e.g., 1/2″ NPT, G1/2). |
3 | Orientation: Align transmitter housing to rotate ±90° for optimal local indicator visibility. Avoid mounting with diaphragm position facing downward. |
4 | Sealing: Apply sealant (e.g., PTFE tape) to male threads. Tighten with proper torque (20 N·m max for 1/2″ NPT). |
5 | Electrical Connection: Use 1/2″ NPT conduit entry. Connect power (10.5–42 V DC) to terminals [+] and [-]. Ensure proper grounding via dedicated ground terminal. |
6 | HART Communication: Connect HART communicator (e.g., YHC5150) in parallel with 250–600Ω resistor for loop configuration. |
7 | Configuration: Set measurement range via local buttons or HART using parameters: LRV (4mA), URV (20mA). Enable damping if required (0–100 sec). |
8 | Pressure Testing: Apply 1.5× rated pressure for hydrostatic test. Check for leaks with soap solution. |
9 | Calibration: Perform zero/span calibration using digital trim function. Verify 4–20mA output corresponds to applied pressure. |
10 | Startup: Gradually pressurize system. Monitor output signal stability (±0.075% of span). |