Customization: | Available |
---|---|
Type: | Rosemount |
Material: | Copper |
Still deciding? Get samples of $ !
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rosemount 3051 High-Precision Pressure Transmitter Terminal Block Technical Manual
Executive Summary
The Rosemount 3051 series pressure transmitter represents Emerson's industry-standard solution for critical pressure, level, and flow measurements. Its terminal block design integrates robust electrical safety, HART® protocol compatibility, and advanced transient protection, ensuring precision in harsh industrial environments. This manual details the terminal specifications, wiring methodologies, and safety protocols for optimal deployment
1. Terminal Block Design & Physical Characteristics
1.1 Configuration Overview
Terminal Layout:
+ / PWR/COMM+: Power supply positive input (24 V DC standard).
- / PWR/COMM-: Negative/power return terminal.
TEST (Optional): Isolated test points excluded from live signal wiring to prevent diode damage
Housing:
NEMA 4X/IP66-rated aluminum or stainless steel enclosure.
Dual-conduit entries with ½-14 NPT threads for EMI shielding and environmental sealing .
1.2 Key Components
Transient Voltage Protection (TVP) Terminal Block:
Requires proper grounding to suppress electrical surges. Non-grounded installations void TVP functionality .
Test Diode Circuit:
Protects against reverse polarity; fails if powered directly (>30 V DC)
2. Electrical Specifications & Compatibility
Parameter | Specification | Notes |
Terminal Identification | (+) PWR/COMM (Positive), (-) PWR/COMM (Negative) | For 4-20 mA HART wiring |
(+) PWR (Positive), PWR- (Negative), Vout/comm+ (Signal output) | For 1-5 Vdc Low-Power HART wiring | |
Wire Requirements | Shielded twisted pair, 24 AWG or larger gauge | Max. length: 5,000 ft (1,500 m) |
Power Supply Voltage | 10.5-42.4 Vdc (4-20 mA HART) | Ripple < 2% |
6-14 Vdc (1-5 Vdc Low-Power HART) | Vout load ≥ 100 kΩ | |
Loop Resistance | ≥ 250 Ω (for HART communication) | Required for HART hand communicator operation |
Test Terminal Voltage | ≤ 30 Vdc | Exceeding voltage may damage test diodes |
Grounding | Housing must be grounded per local regulations | Shield must be insulated from transmitter housing |
Transient voltage protection requires proper grounding | Without grounding, transient protection is ineffective | |
Conduit Sealing | Unused conduit entries must be plugged/sealed | Prevents moisture ingress; drip loops required |
Safety Warnings | - Do not connect powered signal wires to test terminals. | Risk of diode damage [[3][21]] |
- Avoid simultaneous routing of signal/power cables in conduit or cable trays. | Prevents electrical interference | |
- Never remove cover in explosive atmospheres while powered. | Explosion hazard |
2.2 Signal Integrity Protocols
Cabling Requirements:
Shielded twisted-pair (24 AWG min.), max. length: 5,000 ft (1,500 m).
Drip loops mandatory below conduit entries to prevent moisture ingress
Noise Mitigation:
Segregate signal cables from power lines (>1 m separation).
Floating shield or single-point grounding to eliminate ground loops
3. Installation & Wiring Procedures
3.1 Step-by-Step Wiring
Isolate Power: De-energize the loop in hazardous areas before removing the cover
Terminal Access: Remove the field-side housing cover to expose terminals
Lead Connection:
4-20 mA: Connect positive lead to (+), negative to (-).
1-5 V DC: Link +PWR to supply+, PWR- to supply-, signal+ to Vout/comm+
Conduit Sealing: Plug unused entries with NPT-compliant seals to block humidity .
3.2 Power-Up Validation
Loop resistance ≥250 Ω for HART communication .
Multimeter verification: 4 mA (zero pressure) → 20 mA (full scale).
4. Grounding & Transient Protection
4.1 Grounding Best Practices
Shield Grounding:
Bundle and insulate shields to prevent contact with transmitter housing.
Bond shield drains to power supply ground at one point .
Housing Ground:
Earth the enclosure via grounding lug to comply with IEC/CSA standards
4.2 TVP Activation
TVP functions only when:
Transmitter chassis is grounded.
Shield continuity is maintained to the power source .
5. Safety & Compliance Certifications
5.1 Hazardous Environment Protocols
Explosion Prevention:
Never remove covers in explosive atmospheres while powered
IS/FM/ATEX-compliant installations require intrinsic safety barriers .
Leak Prevention:
Tighten process connections before pressurization
5.2 Global Certifications
ATEX, IECEx, FM, CSA, SIL 2/3 (IEC 61508)
CMC/CPA certification for China-manufactured units .
6. Maintenance & Troubleshooting
6.1 Diagnostic Features
HART Diagnostics:
Use HART 7-compatible communicators (e.g., Emerson 475) to verify:
PV (Process Variable), sensor temperature, loop current .
Hardware Checks:
Inspect terminals for corrosion; ensure torque ≤7 in-lb to avoid damage.
6.2 Common Failures & Resolutions
No HART Communication:
Verify loop resistance ≥250 Ω; check shield grounding .
Signal Drift:
Test for moisture ingress or EMI interference from parallel power cables
7. Conclusion
The Rosemount 3051's terminal system delivers unmatched reliability through precision engineering, rigorous safety design, and adaptive electrical compatibility. Its TVP protection, dual-output configurability, and HART integration make it ideal for critical process applications in oil/gas, chemical, and power industries. Adherence to grounding and cabling specifications is paramount to sustain performance in demanding operational environments.
The packaging and transportation of instrumentation in global trade hinges on a synergy of advanced materials, rigorous testing, regulatory compliance, and smart logistics. By adopting hybrid structural designs, leveraging real-time monitoring technologies, and prioritizing sustainability, exporters can ensure the safe, efficient, and cost-effective delivery of precision instruments. Continuous innovation in materials science and IoT integration will further redefine industry standards, enhancing resilience in an increasingly interconnected market.
Q: How long will you give me the reply?
A: We will reply to you as soon as we see the information.
Q: What is the delivery time?
A: Our delivery time is within 3-7 days after we get your payment;
for large qty mass orders, the time should be confirmed again for you.
Q: How about your package?
A: Do not worry about the package, we have rich experience in packing, and all our package is wooden case package.
Q: How about the payment terms?
A: You can choose T/T.
Q: Do you provide samples?
A: Yes, we have materials in stock to help you to get the samples as soon as we can.
Q: What is the MOQ?
A:1PC.
Q: Can I get a lower price if I order large quantities?
A: Yes, cheaper prices with more bigger size orders.