Product Description
Product Description
Product Name | 3051S2TG |
Brand Name | Rosemount |
Warranty | 1 Year |
Website | KeRui(WeiFang)AutomationEquipment Co.,Ltd |
Detailed Photos
Installation Instructions
1. Safety Precautions
1.1 Ensure the work area is free from explosive or hazardous atmospheres. Verify compliance with OSHA, IEC, or regional safety regulations.
1.2 De-energize and isolate the process before installation. Use lockout/tagout (LOTO) procedures to prevent accidental pressurization.
1.3 Wear PPE: heat-resistant gloves, face shields, and flame-retardant clothing when handling high-temperature processes.
1.4 Confirm material compatibility using the Rosemount Material Selection Guide (e.g., 316L stainless steel, Hastelloy®).
1.5 Avoid exposure to excessive RFI/EMI sources. Maintain a minimum distance of 1 m (3 ft) from high-voltage equipment.
2. Unpacking and Inspection
2.1 Inspect the shipping container for punctures, dents, or moisture ingress. Document damages with photographs for carrier claims.
2.2 Cross-check the nameplate details: model 3051S2TG, pressure range, serial number, and Ex certification marks (if applicable).
2.3 Verify process connection specifications against P&ID drawings (e.g., ASME B16.5 flanges, NPT thread dimensions).
3. Mounting the Transmitter
3.1Location Selection:
Mount at least 30 cm (12") above frost lines in outdoor environments to prevent freezing.
For gas applications, position the transmitter above the process tap; for liquids, mount below the tap to prevent gas entrapment.
3.2 Orientation:
Align the diaphragm vertically for liquid services to minimize air bubble formation.
Use a 5° upward tilt for steam applications to facilitate condensate drainage.
3.3 Process Connection:
Apply thread sealant (e.g., PTFE tape) to male NPT threads. Avoid sealant on the first two threads to prevent contamination.
Torque flange bolts in a star pattern to 30-35 ft-lb (40-47 N·m) for 1/2" flanges. Re-torque after 24 hours of thermal cycling.
3.4 Mounting Bracket Installation:
For pipe mounting, use a 2-inch diameter Schedule 40 pipe with a wall thickness ≥ 3.91 mm (0.154").
Secure the U-bolt clamp with 9-11 ft-lb (12-15 N·m) torque to avoid housing deformation.
4. Electrical Wiring
4.1Power Requirements:
Ensure loop impedance ≤ (Vsupply - 10.5V) / 0.022A for proper 4-20 mA operation.
Use Class 1, Division 1 certified barriers in hazardous locations per NEC/CEC guidelines.
4.2 Terminal Connections:
Strip wire insulation to 7-8 mm (0.28-0.31") and insert fully into terminals.
Apply anti-oxidation compound (e.g., Noalox®) to copper conductors in humid environments.
4.3 HART® Communication:
Maintain a 250 Ω minimum load resistance in the loop for HART signal stability.
Use Belden 3079F or equivalent shielded cable with 22-18 AWG conductors.
5. Configuration and Calibration
5.1Initial Setup:
Access the LCD menu: Press + and - buttons simultaneously for 3 seconds to enter configuration mode.
Set damping time (0.2-32.0 sec) to filter noise in pulsating processes.
5.2 Parameter Configuration:
Enable square root extraction for flow measurement (Rangeability ≥ 15:1).
Configure fail-safe mode: Upscale (21.75 mA) or downscale (3.75 mA) on sensor fault.
5.3 Zero Calibration:
Stabilize ambient temperature for 4 hours before calibration.
Use the "Zero Key" function (local pushbutton) for one-touch zero adjustment.
5.4 Span Calibration:
Apply reference pressure using a deadweight tester or ISO 17025-certified calibrator.
Perform 3-point calibration (0%, 50%, 100%) for non-linear compensation.
6. Commissioning
6.1 Leak Test:Pressurize to 1.5× maximum operating pressure for 10 minutes. Acceptable leak rate: ≤ 0.25% FS/min.
6.2 Signal Validation:Measure loop current with a 0.01% resolution multimeter. Tolerance: ±0.075% of span.
6.3 HART Loop Test:Verify PV (Process Variable), SV (Secondary Variable), and TAG address via AMS Suite or FieldXpert.
7. Operation and Maintenance
7.1 Routine Checks:
Quarterly inspection: Clean vent ports with isopropyl alcohol and soft brushes.
Annual validation: Compare transmitter output against master gauges with ±0.02% accuracy.
7.2 Draining Condensate:For steam services, open the drain valve for 5-10 seconds every 8 hours of operation.
7.3 Re-zeroing:Perform after sensor module replacement or process fluid density changes > 10%.
7.4 Firmware Updates:Download firmware from Emerson's Quick Start Update Tool (QSUT). Ensure DCS compatibility before updating.
8. Troubleshooting
8.1No Output Signal:Check reverse polarity protection diode (1N4007) for shorts. Replace if voltage < 9 VDC.
8.2Erratic Readings:
Inspect capillary lines for kinks. Maximum bend radius: 50 mm (2") for 1/4" tubing.
Test sensor module resistance: 2-5 kΩ at 25°C (77°F). Replace if out of tolerance.
8.3HART Communication Failure:Measure HART signal amplitude: 0.5-1.5 Vp-p. Install HART filter if AC noise exceeds 20 mVrms.
9. Technical Specifications
Overpressure Limit: 1.5× URL (Upper Range Limit) without permanent drift.
Long-Term Stability: ±0.1% URL per year.
Response Time: < 100 ms (90% step change).
CE Compliance: EN 61326-1:2013 (EMC), EN 61010-1:2010 (Safety).
SIL Verification: PFDAVG = 0.14 FIT, SFF = 92% per IEC 61508.
Packaging & Shipping
Company Profile
Certifications
FAQ
You may have this questionsQ: How long will you give me the reply?
A: We will reply to you as soon as we see the information
Q: What is the delivery time?
A:The products in stock will be shipped after receiving the payment, and the products that
need to be ordered are subject to the factory time.
Q: How about your package?
A: Do not worry about the package, we have rich experience in packing.
Q: How about the payment terms?
A:You can choose T/T.
Q: What is the MOQ?
A:1PC.
Q: Can l get a lower price if l order large quantities?
A: Yes, cheaper prices with more bigger size orders.
Q:After sales and warranty?
A: We provide one year warranty lifetime technical support services.
Address:
N/a, Weifang, Shandong, China
Business Type:
Trading Company
Business Range:
Instruments & Meters
Company Introduction:
Different kinds of products are available in our company. We′re pleased to get your Inquiry and we will reply you as soon as possible. We stick to the principle of "quality first, service first, continuous improvement and innovation to meet the customers" for the management and "zero defect, zero complaints" as the quality objective.